Protocol- and Frame-Analysis:PROFIBUS DP-V0 and DP-V1, automatic baudrate detection in the range of 9.6 kBit/s .. 12 MBit/s.
Signal-Analysis:PROFIBUS DP-V0, DP-V1, FMS and MPI; signal quality index 0 .. 5,000, determined from signal waveform, signal/noise ratio and rise time; signal sampling with 8/16 samples per bit.
Oscilloscope:Test range: ±5 V at 10 mV resolution (differential), 0 V .. 15 V at 15 mV resolution (A or B to DGND); sampling rate: up to 384 Msamples/s; sampled points: 2,400 (signal details), 8,192 (oscilloscope analysis).
Topology Scan:Active, maximum distance: 230 m, accuracy: ±2 m.
Cable Test:Active, supported cable segment length:
5 m .. 1,500 m, accuracy: 5 %.
3 user-definable network directories (segment and test location) for storing quick tests, trend logs and cable test results, trend logging: max. 99 hours.
IN: L = 0 V .. 0.8 V; H = 2.4 V .. 24 V; pulse > 10 μs, active high; OUT: approximately 5 V, active low (connection to storage oscilloscope).